AirStorm - AS-54 Pro Series Fan Installation Manual

Hog Slat Inc. Newton Grove, NC USA January 2025 14 Air Storm Fans the appropriate voltage every 3 seconds. If the voltage returns to appropriate levels the drive will restart the motor. Failed Start Protection: If the motor fails to start it will attempt to restart after approximately 30 seconds. If the motors experiences subsequent failures it will take 15 seconds longer for every failure experienced up to a maximum of 2 minutes. Ex. If a motor fails to start 3 times it will wait 30 seconds after the first failure, then 45 seconds after the second, then 60 seconds after the third before it attempts to start again. Electrical Installation The fan is intended to be operated from a typical single-phase 230 Vac 60 or 50 Hz line input. The minimum and maximum input voltage range is shown below. Full rated output power is guaranteed between the Minimum Full Performance Voltage and Maximum Operating Voltage. Line Input Minimum Operating Voltage Minimum Full Performance Voltage Maximum Operating Voltage 230 Vac 180 Vac 187 Vac 253 Vac AC Connections Frequency The units will operate at 60/50Hz +/- 5% Special Conditions Related to In-Field Wiring of Air Storm 54” Omni Drive.