AirStorm - AS-57 Pro Series Fan Installation Manual

Hog Slat Inc. Newton Grove, NC USA January 2025 17 Air Storm Fans Over Voltage/Under Voltage: If the drive experiences an over or under voltage then it will shut off the motor to prevent damage. The drive board will check for the appropriate voltage every 3 seconds. If the voltage returns to appropriate levels the drive will restart the motor. Failed Start Protection: In the event of a safety core fault, the motor will attempt to restart after 60 seconds automatically, and retries every 60 seconds until the fault is resolved. Electrical Installation The Unit is intended to be operated from a typical single-phase 230 Vac 60 or 50 Hz line input. The minimum and maximum input voltage range is shown below. Full rated output power is guaranteed between the Minimum Full Performance Voltage and Maximum Operating Voltage. Line Input Minimum Operating Voltage Minimum Full Performance Voltage Maximum Operating Voltage 230 Vac 180 Vac 187 Vac 253 Vac AC Connections Frequency The units will operates at 60/50Hz +/- 5%