AirStorm - AS-57 Pro Series Fan Installation Manual

Hog Slat Inc. Newton Grove, NC USA January 2025 18 Air Storm Fans Special Conditions Related to In-Field Wiring of Air Storm 57” Omni Drive. Logic Board Start control Motor starts when power is applied and DC input voltage signal reaches .9V in 010v operation or 9.3V in 10-0V operation. For analog input the SPEED_SEL dip switch should be in ON position. Motor starts when set to fixed speed mode and power is applied to drive. ! Motor must have a minimum of 1 minute of off time before restarting. Failure to maintain 1 minute of off time before restarts will void warranty ! Adjustable Inputs Rotary switch SW1 Sets motors maximum speed in fixed and variable speed mode. POS 0 1 2 3 4 5 6 7 8 9 RPM 400 433 466 500 533 566 600 633 667 700 Set to position 4, 533 RPM by default.