Hog Slat Inc. Newton Grove, NC USA November 2019 13 Air Storm Fans If you have purchased a product with a VFD Motor please see below! The following motors DO NOT contain internal thermal protection. They are intended to be used in conjunction with a variable frequency drive (Listed in table below). If any of the motors listed below are used in an application where they are not directly controlled by a variable frequency drive, then INSTALLATION/VALIDATION OF EXTERNAL THERMAL PROTECTION IS REQUIRED! EXTERNAL THERMAL PROTECTION SHOULD BE SIZED APPROPRIATELY Please reference NEC 430.31/430.32/430.40 for additional information regarding overload protection sizing. Motor Drive HS9308-VFD HSFI-1001 HS9306A-VFD HSFI-1001 HS9309-VFD HSFI-1001 HS9314-VFD HSFI-1002 HS9378-VFD HSFI-1002 NOTE: Please be aware that when determining wire and or breaker size and layout that fans with phase conversions (Single to Three Phase) should be sized according to the AMP draw of Drive and not the motor. Examples are shown below. Wire size should be appropriate to accommodate Drive’s input rated Amperage. The product is intended to be installed in accordance with all local and national codes. Fan Model Number input Rated Amps AS-14EDDLP-V 8.8A AS-18EDDLP-V 8.8A AS-24EDDLP-V 8.8A AS-36EDDLPA-V 8.8A AS-54XEBDLP-V 13.3A AS-57EBDBP-V 13.3A AS-57EBDBPG-V 13.3A AS-54EDDLP-ID 20.0A WS-F52B2A-V 13.3A WS-54SBDLA-V 13.3A WS-54PBDBG-V 13.3A