Hog Slat Inc. Newton Grove, NC USA AUG 2025 REV A5 17 Ventilation System 15D: HUMIDITY COMPENSATION: Stage 1 fan speed can be automatically increased based on relative humidity levels. Humidity probe is required for this operation. The compensation percentage is the amount of speed increase. Once the humidity is greater than the “Humidity level set point”, the speed of the stage 1 fan will proportionally increase until the humidity is 10% greater than the set point at which time the fan will be running at full compensation level. Example: Minimum speed = 50%, Humidity compensation % = 30. When humidity is equal to or greater than 10% above the humidity level set point, stage 1 fan speed will be (50+30) = 80%. 16. Not Used In the following sections for cooling, heating, mist and alarm settings the controller uses both relative and actual temperatures. In each setting the relative value will be the variable that is adjusted however the actual temperature is displayed alongside the variable to make it easier to determine the actual temperature. ================================================================== 17. COOLING: All stages can provide cooling. Stage 1 is variable speed output while Stages 2-7 are constant speed relay output. 17A 17B 17C 17D 17E 17F 17G