Hog Slat Inc. Newton Grove, NC USA AUG 2025 REV A5 20 Ventilation System 3. HEATER 2 ZONE SETTING: The OFFSET (2) value is the number of degrees below set point the Heater 2 should turn off. The Diff (2) + OFFSET (2) values are the number of degrees below the set-point when the Heater 2 is to turn on. Example above, Set Point = 70F 18C. SELECT HEAT TYPE (CASCADING): If one heater is used, heater will be assigned to Stage 7. Only Heater 1 settings will be highlighted and able to be changed. If two heaters are used, Heater 1 will be assigned to Stage 6 and Heater 2 will be assigned to Stage 7. Both Heater 1 and Heater 2 setting will be highlighted for changes. 1. HEATER 1 SETTING: The OFFSET (1) value is the number of degrees below set point the Heater 1 should turn off. The DIFF (1) + OFFSET (1) values are the number of degrees below the set-point when the Heater 1 is to turn ON. Example above, Set Point = 70F 1 2