Hog Slat - HSVC1016 Ventilation Controller Installation Manual

Hog Slat Inc. Newton Grove, NC USA AUG 2025 REV A5 5 Ventilation System SECTION 2: TECHNICAL SPECIFICATIONS ELECTRICAL RATING: Power Supply 110/120 or 220/240VAC 50/60Hz, single phase. L1 same phase as Stage 1. Fuse 1A fast acting, 250V, F11 Supply Field Wiring: COPPER CONDUCTORS ONLY Probe Inputs: <5V, isolated from the supply. Operating Range -40.0 to 120.0F (-40.0 to 48.9C) Outputs: Stage 1: Variable, 60Hz, 10A FAN (0.5HP @ 115VAC)/(1.5HP @ 230VAC), Fuse 15A slow blow. Stage 1, Fuse F1 0-10 VDC output option to control VFD or ECM speed controlled fan Stage 2 through 7: ON/OFF, 115/230VAC, 60Hz, 30VDC, 6A FAN, 10A RES. Fuse 15A slow blow. Stage 2, Fuse F2 (used for cooling) Stage 3, Fuse F3 (used for cooling) Stage 4, Fuse F4 (used for cooling) Stage 5, Fuse F5 (used for cooling or mist system) Stage 6, Fuse F6 (used for Heating, Cooling or mist system) Stage 7, Fuse F7 (used for Heating, Cooling or mist system) Alarm: Relay output Normally Open/Normally Closed, 115/230VAC, 60Hz, 30VDC, 3A, Fuse 3A slow blow. Fuse F7 Operating conditions: 0 to 40°C (32-104°F), 0-95% RH, non-condensing. Indoor use only. Storage temperature: -20 to 50°C (-4 to 120°F) Altitude: Up to 2000 m (6560 ft) Enclosure: INDOOR USE ONLY