Hog Slat - HSVC1022-2C5A Top Board Installation Manual

Hog Slat Inc. Newton Grove, NC USA MAY 2026 REV IR 22 Ventilation System 2. HEATER 2 SETTING: The DIFF (2) + OFFSET (1) + DIFF (1) is the value of degrees below set point where Heater 2 turns ON. Heater 2 turns OFF at the temperature setting DIFF (1) +OFFSET (1) which is the same as when Heater 1 is to turn ON. Example above, Set Point = 70F 18D. HEATER RUN TIME: Each heater has a resettable accumulated run timer. To reset the timer value, press the block displaying the timer value which will launch a new screen to allow user to reset each timer separately or both simultaneously. The accumulated timer is in hours: minutes and can log up to 9999:59. ================================================================== 19. MIST COOLING: Used to provide additional cooling for animals. Relay output to control misting unit(s). Mist cooling is assigned to the last cooling stage available automatically. If (1) heater is used on Stage 4, mist cooling will be assigned to Stage 3. If no heaters are used, then STAGE 4 will be assigned to Mist cooling. To use Mist cooling, press “ACTIVATE” icon. This will show which output has been assigned as well as launch the mist cooling cycle. During field wiring, it must be known if a heater stage will be used so that mist cooling stage assignment will be known prior to powering up controller. If a heater is being used, then wire stage 3 for mist cooling. 19A: MIST ON TIME: Set to the number of minutes for the misting system to be ON. 19B: MIST OFF TIME: Set to the number of minutes for the misting system to be OFF. 19A 19B 19C 19D 19E 19F