Hog Slat Inc. Newton Grove, NC USA AUG 2025 REV A2 12 Ventilation System Press the MENU button. This will go to the HOME screen. Go through the below listed highlighted in blue buttons to set up the minimum parameters required. NOTE: If you choose not to perform the minimum set up, the controller will default to output stages as cooling with one Heat, Mist cooling, one probe, Stage 1 to curve “1” and non-floating Stage 3. 1. SETTINGS: Assign the appropriate motor curve for Stage 1 fan. (see section 10, item 14E and 14F) 2. HEAT: (see section 10, item 18) assign if Heat 2 is used which is assigned to Stage 3 output. 3. PROBES: (see section 10, item 21). Select the number of probes being used. Once the initial set up is complete, Press the ACTIVATE CONTROLLER button found on the HOME screen. Controller will then begin reading the temperature probes and react accordingly. At this point final set up can be performed in terms of setting up each stage temperature set points, alarms, curves etc...