Hog Slat - HSVC1115F Ventilation Controller Installation Manual

Hog Slat Inc. Newton Grove, NC USA AUG 2025 REV A2 13 Ventilation System SECTION 10: SCREENS AND OPERATION 1. HOME SCREEN 1. PROBE TEMPERATURES AND STATUS: Temperature shown is actual measured temperature for each probe that is active. Probe fault indicator is to the right of each value display. Press any temperature reading and see Highest and Lowest recorded value since last reset. 2. HUMIDITY RH%: Actual measured value. Used for Humidity Compensation and Mist cooling control. 3. SET POINT: Desired temperature set point. Use +/- buttons to the right to adjust. 4. ALARM: Indicator is illuminated in the case of an alarm condition. 5. STAGE INDICATORS: Indicator will illuminate as each stage is activated. 6. OUTDOOR TEMPERATURE: Temperature shown is actual measured temperature if active. Probe fault indicator is to the right of value display. Press any temperature reading and see Highest and Lowest recorded value since last reset. 7. HEATER OUTPUTS: When heaters are selected, this indicator will illuminate when the heater(s) are activated. 8. TEMP & MIN. SPEED CURVE: If Temperature curve has been activated the indicator will be illuminated. 9. HUMIDITY COMPENSATION: Indicator will illuminate when Humidity Compensation is active. 10. TEST MODE ACTIVE: When unit is in test mode this will illuminate. Unit will automatically turn off test mode if there is 5 minutes of inactivity of controller touchscreen. Also, you can press the TEST MODE indicator for a shortcut to the TEST page. 1 2 3 4 5 6 7 8 9 14 15 16 17 18 19 20 21 22 10 11 12 13