Hog Slat Inc. Newton Grove, NC USA AUG 2025 REV A2 17 Ventilation System full compensation level. Example: Minimum speed = 50%, Humidity compensation % = 30. When humidity is equal to or greater than 10% above the humidity level set point, stage 1 fan speed will be (50+30) = 80%. ================================================================== 16. CURTAIN OPERATION 16A: CURTAIN MACHINE OPERATION: Selection for Automatic or Manual operation. Indicator above shows mode currently selected. If manual mode, the curtain direction is also displayed. In AUTO mode curtain machine control is performed by controller based on temperature settings. 16B: DEAD BAND: Temperature range the curtain has no movement. When temperature is above the OPEN temperature, the curtain will continue to open. When temperature drop 0.3F below the OPEN temperature the curtain will stop. As temperature falls equal to and below the CLOSE temperature the curtain will continue to close. If temperature rise 0.3F above the CLOSE temperature the curtain will stop movement. 16C: CYCLE TIME: Defines the time on and time when temperature 16A 16D 16B 16C 16E