Hog Slat Inc. Newton Grove, NC USA AUG 2025 REV A2 20 Ventilation System 18A. SELECT HEAT STAGE(S): Press the icon only if a second heater to be used. If two heaters are to be used, press “2 Heaters” icon (Icon will turn green). To deselect heater choice, press the icon again and it will turn gray indicating it has been unselected. 18B. SELECT HEAT TYPE (ZONES): Press the icon for the heater arrangement. For ZONES press the “ZONES” icon which will turn green. Zone heating is when heaters are placed in different areas or rooms. Each heater operates independently and is controlled based on the Differential and Offset temperatures to control when they turn on and off as compared to the set point temperature. Probes 1 and 2 are assigned to Heater 1 and probes 3 and 4 are assigned to Heater 2. Probes can be turned off or not connected individually however if two heaters are used in zones mode, then a minimum of 2 probes are required, one for each zone. When two probes are used (one in each zone) probe 1 = Heater 1 and probe 3 = Heater 2. If two probes are used for each heating zone, the average temperature between the two probes is used. Probe 1 and Probe 2 = Heater 1. Probe 3 and Probe 4 = Heater 2. NOTE: In order to select ZONES heating, “2 Heaters” must be selected first and at least two probes connected, one for each zone. 18A 18B 18C 18D