Hog Slat - HSVC1115F Ventilation Controller Installation Manual

Hog Slat Inc. Newton Grove, NC USA AUG 2025 REV A2 22 Ventilation System If two heaters are used, Heater 1 will be assigned to dedicated Heat 1 output and Heater 2 will be assigned to Stage 3. Both Heater 1 and Heater 2 setting will be highlighted for changes. 1. HEATER 1 SETTING: The OFFSET (1) value is the number of degrees below set point the Heater 1 should turn off. The DIFF (1) + OFFSET (1) values are the number of degrees below the set-point when the Heater 1 is to turn ON. Example above, Set Point = 70F 2. HEATER 2 SETTING: The DIFF (2) + OFFSET (1) + DIFF (1) is the value of degrees below set point where Heater 2 turns ON. Heater 2 turns OFF at the temperature setting DIFF (1) +OFFSET (1) which is the same as when Heater 1 is to turn ON. Example above, Set Point = 70F 18D. HEATER RUN TIME: Each heater has a resettable accumulated run timer. To reset the timer value, press the block displaying the timer value which will launch a new screen to allow user to reset each timer separately or both simultaneously. The accumulated timer is in hours: minutes and can log up to 9999:59. ================================================================== 1 2