Hog Slat - HSVC1115F Ventilation Controller Installation Manual

Hog Slat Inc. Newton Grove, NC USA AUG 2025 REV A2 26 Ventilation System activated. Once the final day entry is reached, the controller will hold that temperature until the temperature curve is re-activated. Rules for entries Highest day entry 999 First day entry must start at the lowest day number. Day number entries must always increase for each of the following data row entries. Typically the highest temperature will be on the first day entry (first row of data) and decrease. However note the temperature entries can increase or decrease. Maximum deviation in temperature between day entries is 4F (2.2C) Minimum ventilation curve follows the same day number as the temperature curve and is active simultaneously with the temperature curve. Minimum ventilation curve sets the minimum speed of the Stage 1 fan for each day entry. 22A: TEMPERATURE/DAY CURVE INPUTS: Press the block for the day entry# or the temperature entry#. A keyboard will pop up to enter the value. Once the value is selected, press enter on the keyboard screen. Continue entering a day value and temperature value for all 6 entries. DO NOT LEAVE ANY BLANK. If the temperature is not to change after less than 6 entries, then enter the same temperature for following day entries. 22A 22B 22D 22C 22E