Hog Slat Inc. Newton Grove, NC USA AUG 2025 REV A2 33 Ventilation System SECTION 17: CONTROLLER PARAMETER VALUES PARAMETER DEFAULT MIN. MAX. USER VALUE TEMPERATURE SET POINT (C OR F) 75F EMPTY BARN (C OR F) 32F -40 120 STAGE 1 MIN SPEED % 50% 10 100 MIN. VENT CYCLE ON TIME (SEC.) 60 0 900 MIN. VENT CYCLE OFF TIME (SEC.) 240 0 900 HUMIDITY COMPENSATION % 20% 0 100 HUMIDITY LEVEL SET POINT % 65% 40 100 BW STAGE 1 (C OR F) 2F 0.3 20 DIFF STAGE 2 2F 0.3 20 DIFF STAGE 3 2F 0.3 20 STAGE 3 FLOATING? NO STAGE 3 OFFSET (FLOATING ONLY) 0 0 20 CURTAIN DEAD BAND (C OR F) 2F 0.3 20 CURTAIN CYCLE TIME (TIME ON) (SEC) 20 0 900 CURTAIN CYCLE TIME (TIME OFF) (SEC) 80 0 900 OUTSIDE TEMP. (CURTAIN COMP.) (C OR F) 70F -40 120 CLOSE INLETS ON CURTAIN OPEN NO MIST ON TIME (MIN.) 1 0 60 MIST OFF TIME (MIN.) 10 0 60 MAX HUMIDITY CUT OFF (%) 95% 40 100 MIST COOLING OFFSET (C OR F) 14F 0.3 40 MIST COOLING DIFF. (C OR F) 2F 0.3 20 MAX ZONE TEMP DIFF (C OR F) 7.5F 0 40 HEATER 1 DIFF (C OR F) 2.0F 0. 3 20 HEATER 1 & 2 OFFSET (C OR F) 2.0F -20 30 HEATER 2 DIFF (C OR F) 2.0F 0.3 20 HEATER 2 ZONE DIFF (C OR F) 2.0F 0.3 20 HEATER 2 ZONE OFFSET (C OR F) 2.0F -20 30 EMPTY BARN ALARM (C OR F) 32F -40 100 ALARM HIGH OFFSET (C OR F) 12F 0.5 40 ALARM LOW OFFSET (C OR F) 10F 0.5 40 CRITICAL TEMPERATURE (C OR F) 95F -40 120